Keterangan Barangan | EARTH LEAKAGE RELAY |
Kod Barangan | EE031202.ME118.A130 |
Nama Syarikat | MIKRO SDN. BHD (FORMERLY KNOWN AS MIKRO BERHAD) |
Status Syarikat | PENGILANG |
Alamat | NO. 3, JALAN ANGGERIK MOKARA 31/48, SEKSYEN 31, KOTA KEMUNING |
| 40460 SHAH ALAM SELANGOR |
No Telefon | 0355253863 |
No Fax | 0355253873 |
Email | mikro@itmikro.com |
Website | www.itmikro.com |
Jenama | MIKRO |
No Laporan | LAPORAN UJIAN SIRIM : 2024RE0134 |
Tarikh Tamat | 15-06-2027 |
Rujukan | i) SAFETY STANDARD: IEC 60255-27:2013 (CLAUSE10.6.4.2 IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 DIELECTRIC TEST)
ii) EMC STANDARD: IEC 60255-26:2013 (CLAUSE 5.1, 7.2.3, 7.2.4, 7.2.5, 7.2.6, 7.2.7, 7.2.8, 7.2.9, 7.2.10, 7.2.11, 7.2.12 & 7.2.13) |
Catatan | Sijil ISO 14001 (Tarikh Tamat: 23.08.2026)
i) COMMUNICATION INTERFACE: NO
ii) COMMUNICATION PROTOCOL: NO
iii) COMMUNICATION DEVICE: NO
iv) REMOTE REAL TIME MONITORING AND MANAGEMENT SYSTEM:NO
v) AMBIENT TEMPERATURE: -5°C TO 55°C (DIN 310 & DIN 310E), -10°C TO 55°C (DIN 300, DIN 300E & DIN 330)
vi) RELATIVE HUMIDITY: 93% (DIN 310 & DIN 310E), 5% TO 95% (DIN 300, DIN 300E & DIN 330)
vii) DEGREE OF PROTECTION: NO
viii) FAULT RECORD: YES (DIN 310, DIN 310E & DIN 330)
ix) BUILT-IN SELF-TEST/DIAGNOSTIC: NO
x) EXTERNAL ALARM CONTACT FOR PROTECTION RELAY FAILURE/DEFECT: NO
xi) OTHER(S): MODEL INI MESTI MENGGUNAKAN ZCT JENAMA MIKRO SAHAJA
|
Bil | TIME DELAY SETTING RANGES | Column Name | SENSITIVITY SETTING RANGES | Model | MOUNTING TYPE | OPERATING VOLTAGE | Gambar |
1 | 0s, 50ms, 100ms, 150ms, 250ms, 350ms, 500ms, 1s & 3s | | 30mA, 50mA, 75mA, 100mA, 125mA, 150mA, 200mA, 250mA, 300mA, 500mA, 750mA, 1A, 1.25A, 1.50A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5A, 15A, 20A, 25A, 30A | DIN 300 | DIN RAIL | 1. Input Voltage Range:
DIN 300-240A : 198 ~ 265V AC
DIN 300-110A : 94 ~ 127V AC
2. Rated Frequency : 50/60Hz | |
2 | 0s, 50ms, 100ms, 150ms, 250ms, 350ms, 500ms, 1s & 3s | | 30mA, 50mA, 75mA, 100mA, 125mA, 150mA, 200mA, 250mA, 300mA, 500mA, 750mA, 1A, 1.25A, 1.50A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5A, 15A, 20A, 25A, 30A | DIN 300E | DIN RAIL
| 1. Input Voltage Range:
DIN 300E-240A : 198~265 VAC
DIN 300E-110A : 94~127 VAC
2. Rated Frequency: 50/60Hz
3. Features:
REMOTE RESET, REMOTE TEST, PRE-FAULT & OUTPUT CONTACT | |
3 | 0s, 0.1s~3s (Step=0.1s) | | 30mA, 50mA,
0.10~1.00A (Step = 50mA),
1.00~10.00A (Step = 1.00A) | DIN 310 | DIN RAIL | 1. Input Voltage Range:
DIN 310-230(6) : 184 ~ 276 VAC
2. Rated Frequency : 50/60Hz | |
4 | 0s, 0.1s~3s (Step=0.1s) | | 30mA, 50mA,
0.10~1.00A (Step = 50mA),
1.00~10.00A (Step = 1.00A) | DIN 310E | DIN RAIL | 1. Input Voltage Range: DIN 310E-230(6) : 184~276 VAC
2. Rated Frequency: 50/60Hz
3. Features:
REMOTE RESET, POSITIVE SAFETY OUTPUT CONTACT & PRE-FAULT OUTPUT CONTACT | |
5 | 0s, 0.1s~3s (Step=0.1s) | | 30mA, 50mA,
0.10~1.00A (Step = 50mA),
1.00~10.00A (Step = 1.00A) | DIN 330 | DIN RAIL | 1. Input Voltage Range:
DIN 330-230A(6) : 184 ~ 276 VAC
2. Rated Frequency: 50/60Hz
3. Features:
AUTO RECLOSE & REMOTE RESET | |