MAKLUMAT BAHAN/BARANGAN YANG DILULUSKAN

Keterangan BaranganEARTH LEAKAGE RELAY
Kod BaranganEE031202.ME118.A130
Nama SyarikatMIKRO SDN. BHD (FORMERLY KNOWN AS MIKRO BERHAD)
Status SyarikatPENGILANG
AlamatNO. 3, JALAN ANGGERIK MOKARA 31/48, SEKSYEN 31, KOTA KEMUNING
40460 SHAH ALAM SELANGOR
No Telefon0355253863
No Fax0355253873
Emailmikro@itmikro.com
Websitewww.itmikro.com
JenamaMIKRO
No LaporanLAPORAN UJIAN SIRIM : 2024RE0134
Tarikh Tamat15-06-2027
Rujukani) SAFETY STANDARD: IEC 60255-27:2013 (CLAUSE10.6.4.2 IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 DIELECTRIC TEST) ii) EMC STANDARD: IEC 60255-26:2013 (CLAUSE 5.1, 7.2.3, 7.2.4, 7.2.5, 7.2.6, 7.2.7, 7.2.8, 7.2.9, 7.2.10, 7.2.11, 7.2.12 & 7.2.13)
CatatanSijil ISO 14001 (Tarikh Tamat: 23.08.2026) i) COMMUNICATION INTERFACE: NO ii) COMMUNICATION PROTOCOL: NO iii) COMMUNICATION DEVICE: NO iv) REMOTE REAL TIME MONITORING AND MANAGEMENT SYSTEM:NO v) AMBIENT TEMPERATURE: -5°C TO 55°C (DIN 310 & DIN 310E), -10°C TO 55°C (DIN 300, DIN 300E & DIN 330) vi) RELATIVE HUMIDITY: 93% (DIN 310 & DIN 310E), 5% TO 95% (DIN 300, DIN 300E & DIN 330) vii) DEGREE OF PROTECTION: NO viii) FAULT RECORD: YES (DIN 310, DIN 310E & DIN 330) ix) BUILT-IN SELF-TEST/DIAGNOSTIC: NO x) EXTERNAL ALARM CONTACT FOR PROTECTION RELAY FAILURE/DEFECT: NO xi) OTHER(S): MODEL INI MESTI MENGGUNAKAN ZCT JENAMA MIKRO SAHAJA
Negara MALAYSIA

BilTIME DELAY SETTING RANGESColumn NameSENSITIVITY SETTING RANGESModelMOUNTING TYPEOPERATING VOLTAGEGambar
10s, 50ms, 100ms, 150ms, 250ms, 350ms, 500ms, 1s & 3s30mA, 50mA, 75mA, 100mA, 125mA, 150mA, 200mA, 250mA, 300mA, 500mA, 750mA, 1A, 1.25A, 1.50A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5A, 15A, 20A, 25A, 30ADIN 300DIN RAIL1. Input Voltage Range: DIN 300-240A : 198 ~ 265V AC DIN 300-110A : 94 ~ 127V AC 2. Rated Frequency : 50/60Hz
20s, 50ms, 100ms, 150ms, 250ms, 350ms, 500ms, 1s & 3s30mA, 50mA, 75mA, 100mA, 125mA, 150mA, 200mA, 250mA, 300mA, 500mA, 750mA, 1A, 1.25A, 1.50A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5A, 15A, 20A, 25A, 30ADIN 300EDIN RAIL 1. Input Voltage Range: DIN 300E-240A : 198~265 VAC DIN 300E-110A : 94~127 VAC 2. Rated Frequency: 50/60Hz 3. Features: REMOTE RESET, REMOTE TEST, PRE-FAULT & OUTPUT CONTACT
30s, 0.1s~3s (Step=0.1s)30mA, 50mA, 0.10~1.00A (Step = 50mA), 1.00~10.00A (Step = 1.00A)DIN 310DIN RAIL1. Input Voltage Range: DIN 310-230(6) : 184 ~ 276 VAC 2. Rated Frequency : 50/60Hz
40s, 0.1s~3s (Step=0.1s)30mA, 50mA, 0.10~1.00A (Step = 50mA), 1.00~10.00A (Step = 1.00A)DIN 310EDIN RAIL1. Input Voltage Range: DIN 310E-230(6) : 184~276 VAC 2. Rated Frequency: 50/60Hz 3. Features: REMOTE RESET, POSITIVE SAFETY OUTPUT CONTACT & PRE-FAULT OUTPUT CONTACT
50s, 0.1s~3s (Step=0.1s)30mA, 50mA, 0.10~1.00A (Step = 50mA), 1.00~10.00A (Step = 1.00A)DIN 330DIN RAIL1. Input Voltage Range: DIN 330-230A(6) : 184 ~ 276 VAC 2. Rated Frequency: 50/60Hz 3. Features: AUTO RECLOSE & REMOTE RESET