MAKLUMAT BAHAN/BARANGAN YANG DILULUSKAN

Keterangan BaranganCOMBINED OVERCURRENT AND EARTH FAULT RELAY
Kod BaranganEE031201.ME650.A130
Nama SyarikatMIKRO SDN. BHD.
Status SyarikatPENGILANG
AlamatNO. 3, JALAN ANGGERIK MOKARA 31/48, SEKSYEN 31, KOTA KEMUNING
40460 SHAH ALAM SELANGOR
No Telefon0355253863
No Fax0355253873
Emailmikro@itmikro.com
Websitewww.itmikro.com
JenamaMIKRO
No LaporanLAPORAN UJIAN SIRIM : 2024RE0133
Tarikh Tamat15-06-2026
Rujukani) SAFETY STANDARD : IEC 60255-27:2013 (10.6.4.2 IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 DIELECTRIC TEST); ii) EMC STANDARD : IEC 60255-26:2013 (CLAUSE 5.1, 7.2.3, 7.2.4, 7.2.5, 7.2.6, 7.2.7, 7.2.8, 7.2.9, 7.2.10, 7.2.11, 7.2.12 & 7.2.13)
Catatani) COMMUNICATION INTERFACE : NO; ii) COMMUNICATION PROTOCOL : NO; iii) COMMUNICATION DEVICE : NO; iv) REMOTE REAL TIME MONITORING AND MANAGEMENT SYSTEM : NO; v) AMBIENT TEMPERATURE : -10 °C TO 55 °C; vi) RELATIVE HUMIDITY : 5% TO 95%; vii) DEGREE OF PROTECTION : IP 54 AT PANEL; viii) FAULT RECORD : YES; ix) EVENT RECORD : NO; x) BUILT-IN SELF-TEST/DIAGNOSTIC : NO; xi) EXTERNAL ALARM CONTACT FOR PROTECTION RELAY FAILURE/DEFECT : NO; xii) OTHER(S) : -
Negara MALAYSIA

BilMODELOPERATING VOLTAGETYPE OF PROTECTIONTIME DELAY SETTING RANGESCURRENT SETTING RANGESGambar
1R 1000198 VAC ~ 265 VAC, 50/60 HzOVER CURRENTa) LOW SET TIME DELAY SETTING (t>): i) TMS FOR INVERSE TIME DELAY: 0.01 TO 1 ii) DELAY FOR DEFINITE TIME: 0.03 s TO 100 s; ________________________________ b) HIGH SET TIME DELAY SETTING (t>>>): i) DELAY FOR DEFINITE TIME: 0.03 s TO 100 s a) LOW SET OVER CURRENT SETTING (I>): 10% TO 250% OF In; _______________________________ b) HIGH SET OVER CURRENT SETTING (I>>>):10% TO 2000% OF In
2R 1000198 VAC ~ 265 VAC, 50/60 HzEARTH FAULTa) LOW SET TIME DELAY SETTING (tIo>): i) TMS FOR INVERSE TIME DELAY: 1.1 TO 1; ii) DELAY FOR DEFINITE TIME: 0.03 s TO 100 s ________________________________ b) HIGH SET TIME DELAY SETTING (tIo>>): i) DELAY FOR DEFINITE TIME: 0.03 s TO 100 sa) LOW SET EARTH FAULT SETTING (Io>): 2% TO 200% OF In _______________________________ b) HIGH SET EARTH FAULT SETTING (Io>>): 2% TO 1000% OF In
Senarai Dokumen Berkaitan :