MAKLUMAT BAHAN/BARANGAN YANG DILULUSKAN

Keterangan BaranganEARTH FAULT RELAY
Kod BaranganEE031204.ME118.A130
Nama SyarikatMIKRO SDN. BHD (FORMERLY KNOWN AS MIKRO BERHAD)
Status SyarikatPENGILANG
AlamatNO. 3, JALAN ANGGERIK MOKARA 31/48, SEKSYEN 31, KOTA KEMUNING
40460 SHAH ALAM SELANGOR
No Telefon0355253863
No Fax0355253873
Emailmikro@itmikro.com
Websitewww.itmikro.com
JenamaMIKRO
No LaporanLAPORAN UJIAN SIRIM: 2022RE0105-M1 SIJIL UJIAN SIRIM: 2022/RFEMCT/TC0002
Tarikh Tamat15-10-2027
Rujukani) SAFETY STANDARD: IEC 60255-27:2013 (CLAUSE 10.6.4.2 - IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 - DIELECTRIC TEST) ii) EMC STANDARD: IEC 60255-26:2013 (CLAUSE 5.1, 7.2.3, 7.2.4, 7.2.5, 7.2.6, 7.2.7, 7.2.8, 7.2.10 & 7.2.11)
CatatanSijil ISO 14001 (Tarikh Tamat: 23.08.2026) i) COMMUNICATION INTERFACE: WIRELESS NFC; ii) COMMUNICATION PROTOCOL: ISO/IEC 15693; iii) COMMUNICATION DEVICE: ANDROID VERSION 10 & ABOVE BASED MOBILE PHONE WITH NFC MODULE READY; iv) REMOTE REAL TIME MONITORING AND MANAGEMENT SSYSTEM: NO; v) AMBIENT TEMPERATURE: -10°C TO 55°C; vi) RELATIVE HUMIDITY: 5% TO 95%; vii) DEGREE OF PROTECTION: IP 54 AT PANEL; viii) FAULT RECORD: YES; ix) EVENT RECORD: YES; x) BUILT-IN SELF-TEST/DIAGNOSTIC: YES (INTERNAL RELAY FAILURE-IRF); xi) EXTERNAL ALARM CONTACT FOR PROTECTION RELAY FAILURE/DEFECT: YES; xii) OTHER(S):-
Negara MALAYSIA

BilMODELTIME DELAY SETTING RANGESCURRENT SETTING RANGESTYPE OF PROTECTIONOPERATING VOLTAGEGambar
1RX 232a) LOW SET TIME DELAY SETTING (tIo>): i) TMS FOR INVERSE TIME DELAY: 0.01 TO 1; ii) DELAY FOR DEFINITE TIME: 0.03 s TO 100 s; ______________________________ b) HIGH SET TIME DELAY SETTING (tIo>>): i) DELAY FOR DEFINITE TIME: 0.03 s TO 100 sa) LOW SET EARTH FAULT SETTING (Io>): 2% TO 200% OF In; ________________________ b) HIGH SET EARTH FAULT SETTING (Io>>): 2% TO 1000% OF InEARTH FAULT198 VAC ~ 265 VAC, 50/60Hz
Senarai Dokumen Berkaitan :