MODEL | KETERANGAN BAHAN/BARANGAN | POWER SUPPLY | CURRENT SETTING RANGES | TIME DELAY SETTING RANGES |
X20 | EARTH FAULT RELAY (INVERSE/DEFINITE TIME DELAY/IDMT) | OPERATING VOLTAGE:
X20-EFR-240AD:
85~265 VAC OR 110~370 VDC | i) LOW SET CURRENT(Io>):
0.02 TO 2 X Ion, 0.5 X Ion FOR IDMT;
ii) HIGH SET CURRENT(Io>>):
0.1 TO 10 x Ion | i) LOW SET DELAY TIME(tIo>):
0.00s TO 100s;
ii) HIGH SET DELAY TIME(tIo>>):
0.00s TO 100s;
iii) TMS (ktIo): 0.01 TO 1.00 |
N201 | EARTH FAULT RELAY (DEFINITE TIME/DT) | OPERATING VOLTAGE:
N201-240AD:
85~265 VAC OR 110~370 VDC | i) LOW SET CURRENT (I>):
0.1 TO 2.0A (2% TO 40%);
ii) HIGH SET CURRENT (I>>):
I> TO 10xI> | i) LOW SET DELAY TIME (DELAY):
0.05s TO 1.0s;
ii) HIGH SET DELAY TIME (t>>):
INSTANTANEOUS |
N202 | EARTH FAULT RELAY (INVERSE/DEFINITE TIMR DELAY/IDMT) | OPERATING VOLTAGE:
N202-240AD:
85~265 VAC OR 110~370 VDC | i) LOW SET CURRENT (I>):
0.1A TO 2.0A (2% TO 40%);
ii) HIGH SET CURRENT(I>>):
I> TO 10xI> | i) LOW SET TMS (TM): 0.05 TO 1.0;
ii) HIGH SET DELAY TIME (t>>): INSTANTANEOUS |