1 | RX 232 | 198 VAC ~ 265 VAC, 50/60Hz | EARTH FAULT RELAY | a) LOW SET TIME DELAY SETTING (tIo>):
i) TMS FOR INVERSE TIME DELAY: 0.01 TO 1;
ii) DELAY FOR DEFINITE TIME: 0.03 s TO 100 s;
______________________
b) HIGH SET TIME DELAY SETTING (tIo>>):
i) DELAY FOR DEFINITE TIME: 0.03 s TO 100 s | a) LOW SET EARTH FAULT SETTING (Io>): 2% TO 200% OF In;
______________________
b) HIGH SET EARTH FAULT SETTING (Io>>): 2% TO 1000% OF In |