MAKLUMAT BAHAN/BARANGAN TAMAT KELULUSAN

Keterangan BaranganCOMBINED OVERCURRENT AND EARTH FAULT RELAY
Kod BaranganEE031201.ME118.A130
SyarikatMIKRO SDN. BHD (FORMERLY KNOWN AS MIKRO BERHAD)
AlamatNO. 3, JALAN ANGGERIK MOKARA 31/48, SEKSYEN 31, KOTA KEMUNING
No Telefon0355253863
No Fax0355253873
JenamaMIKRO
Bil LaporanNot set
Tarikh Tamat15-10-2025
RujukanIEC 60255-26:2013, IEC 60255-27 (CLAUSE 10.6.4.2 - IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 - DIELECTRIC TEST)
CatatanNot set
Negara Pengilang MALAYSIA

TYPE OF PROTECTIONMODELKETERANGAN BAHAN/BARANGANPOWER SUPPLYTIME DELAY SETTING RANGESCURRENT SETTING RANGESGambar
OVERCURRENT PROTECTION & EARTH FAULT PROTECTIONX60COMBINED OVERCURRENT & EARTH FAULT RELAY (INVERSE/DEFINITE TIME DELAY/IDMT)OPERATING VOLTAGE: X60-OCEF-240AD: 85~265 VAC OR 110~370 VDCOVERCURRENT PROTECTION: i) LOW SET DELAY TIME (tI>): 0.00s TO 100s; ii) HIGH SET DELAY TIME (tI>>): 0.00s TO 100s; iii) VERY HIGH SET DELAY TIME (tI>>>): 0.00s TO 100s; iv) TMS (ktI): 0.01 TO 1.00; EARTH FAULT PROTECTION: i) LOW SET DELAY TIME (tIo>): 0.00s TO 100s; ii) HIGH SET DELAY TIME (tIo>>): 0.00s TO 100s; iii) TMS (ktIo): 0.01 TO 1.00OVERCURRENT PROTECTION: i) LOW SET CURRENT, (I>): 0.1 TO 25 X In, 2 X In (FOR IDMT); ii) HIGH SET CURRENT, (I>>): 0.5 TO 40 X In; iii) VERY HIGH SET CURRENT (I>>>): 0.5 TO 40 X In; EARTH FAULT PROTECTION: i) LOW SET CURRENT, (Io>): 0.02 TO 2 X Ion, 0.5 X Ion FOR IDMT; ii) HIGH SET CURRENT, (Io>>): 0.1 TO 10 X In
OVERCURRENT PROTECTION & EARTH FAULT PROTECTIONMK3000L COMBINED OVERCURRENT & EARTH FAULT RELAY (INVERSE/DEFINITE TIME DELAY/IDMT)OPERATING VOLTAGE: MK3000L-240AD: 85~265 VAC OR 110~370 VDC OVERCURRENT PROTECTION: i) LOW SET DELAY TIME (tI>): 0.00s TO 100s; ii) HIGH SET DELAY TIME (tI>>): 0.00s TO 100s; iii) VERY HIGH SET DELAY TIME (tI>>>): 0.00s TO 100s; iv) TMS (ktI): 0.01 TO 1.00; EARTH FAULT PROTECTION: i)LOW SET DELAY TIME (tIo>): 0.00s TO 100s; ii) HIGH SET DELAY TIME (tIo>>): 0.00s TO 100s; iii) TMS (ktIo): 0.01 TO 1.00OVERCURRENT PROTECTION: i) LOW SET CURRENT, (I>): 0.1 TO 25 X In, 2 X In (FOR IDMT); ii) HIGH SET CURRENT, (I>>): 0.5 TO 40 X In; iii) VERY HIGH SET CURRENT (I>>>): 0.5 TO 40 X In; EARTH FAULT PROTECTION: i) LOW SET CURRENT, (Io>): 0.02 TO 2 X Ion, 0.5 X Ion (FOR IDMT); ii) HIGH SET CURRENT, (Io>>): 0.1 TO 10 X In; iii) VERY HIGH SET CURRENT (Io>>>): 0.1 TO 10 X In
Senarai Dokumen Berkaitan :