Bil | MODEL | "RATED CURRENT (A)" | UTILIZATION CATEGORY | NO. OF POLE | Icu (kA) | "Ics (kA) (Ics = 100% Icu)" | TRIP UNIT | SETTING OF PROTECTION | "WEIGHT (kg) (approx.)" | Column Name | Column Name | 1 | HMS040JR
| 40 | A | 3 | 50 | 50 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (16,…,40)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,15)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE | 1.40 | | | 2 | HMS100JR
| 100 | A | 3 | 50 | 50 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (40,…,100)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,15)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE | 1.40 | | | 3 | HMS160JR
| 160 | A | 3 | 50 | 50 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (63,…,160)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,11)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE | 1.40 | | | 4 | HMS041JR
| 40 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS040JR | 1.70 | | | 5 | HMS101JR
| 100 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS100JR | 1.70 | | | 6 | HMS161JR
| 160 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS160JR | 1.70 | | | 7 | HHT040JR
| 40 | A | 3 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HMS040JR | 2.00 | | | 8 | HHT100JR
| 100 | A | 3 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HMS100JR | 2.00 | | | 9 | HHT160JR
| 160 | A | 3 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HMS160JR | 2.00 | | | 10 | HHT250JR
| 250 | A | 3 | 25 | 25 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (90,…,250)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,11)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE | 2.00 | | | 11 | HHT041JR
| 40 | A | 4 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HMS040JR | 2.40 | | | 12 | HHT101JR
| 100 | A | 4 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HMS100JR | 2.40 | | | 13 | HHT161JR
| 160 | A | 4 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HMS160JR | 2.40 | | | 14 | HHT251JR
| 250 | A | 4 | 25 | 25 | ELECTRONIC
| SAMA SEPERTI MODEL HHT250JR | 2.40 | | | 15 | HMT040JR
| 40 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS040JR | 2.00 | | | 16 | HMT100JR
| 100 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS100JR | 2.00 | | | 17 | HMT160JR
| 160 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS160JR | 2.00 | | | 18 | HMT250JR
| 250 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HHT250JR | 2.00 | | | 19 | HMT041JR
| 40 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS040JR | 2.40 | | | 20 | HMT101JR
| 100 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS100JR | 2.40 | | | 21 | HMT161JR
| 160 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HMS160JR | 2.40 | | | 22 | HMT251JR
| 250 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HHT250JR | 2.40 | | | 23 | HNW250JR
| 250 | A | 3 | 40 | 40 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (90,…,250)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,12)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE | 3.10 | | | 24 | HNW400JR
| 400 | A | 3 | 40 | 40 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (160,…,400)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,12)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE
| 3.10 | | | 25 | HNW630JR
| 630 | A | 3 | 40 | 40 | ELECTRONIC
| CURRENT SETTING
A) LONG TIME PROTECTION, Ir= Ir1 X Ir2= (250,…,630)X(0.91,…,1)
B) SHORT TIME PROTECTION, Isd=OFF,=Ir X (1.5,…,10)
C) INSTANTANEOUS PROTECTION, Ii=In X (3,…,11)
D) TIME SETTING INVERSE TIME DELAY, tr =ADJUSTABLE
E) SHORT TIME DELAY, tsd = ADJUSTABLE
| 3.10 | | | 26 | HNW251JR
| 250 | A | 4 | 40 | 40 | ELECTRONIC
| SAMA SEPERTI MODEL HNW250JR | 3.60 | | | 27 | HNW401JR
| 400 | A | 4 | 40 | 40 | ELECTRONIC
| SAMA SEPERTI MODEL HNW400JR | 3.60 | | | 28 | HNW631JR
| 630 | A | 4 | 40 | 40 | ELECTRONIC
| SAMA SEPERTI MODEL HNW630JR | 3.60 | | | 29 | HMW250JR
| 250 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HNW250JR | 3.10 | | | 30 | HMW400JR
| 400 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HNW400JR | 3.10 | | | 31 | HMW630JR
| 630 | A | 3 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HNW630JR | 3.10 | | | 32 | HMW251JR
| 250 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HNW250JR | 3.60 | | | 33 | HMW401JR
| 400 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HNW400JR | 3.60 | | | 34 | HMW631JR
| 630 | A | 4 | 50 | 50 | ELECTRONIC
| SAMA SEPERTI MODEL HNW630JR | 3.60 | | |
|