MAKLUMAT BAHAN/BARANGAN YANG DILULUSKAN

Keterangan BaranganEARTH LEAKAGE RELAY
Kod BaranganEE031202.ME118.A130
Nama SyarikatMIKRO SDN. BHD (FORMERLY KNOWN AS MIKRO BERHAD)
Status SyarikatPENGILANG
AlamatNO. 3, JALAN ANGGERIK MOKARA 31/48, SEKSYEN 31, KOTA KEMUNING
40460 SHAH ALAM SELANGOR
No Telefon0355253863
No Fax0355253873
Emailmikro@itmikro.com
Websitewww.itmikro.com
JenamaMIKRO
No LaporanLAPORAN UJIAN SIRIM : 2022RE0470
Tarikh Tamat15-06-2025
Rujukani) SAFETY STANDARD : IEC 60255-27:2013 (10.6.4.2 IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 DIELECTRIC TEST); ii) EMC STANDARD : IEC 60255-26:2013 (CLAUSE 5.1, 7.2.3, 7.2.4, 7.2.5, 7.2.6, 7.2.7, 7.2.8, 7.2.10 & 7.2.11)
CatatanSijil ISO 14001 (Tarikh Tamat: 23.08.2026) i) COMMUNICATION INTERFACE : WIRELESS NFC; ii) COMMUNICATION PROTOCOL : ISO/IEC 15693; iii) COMMUNICATION DEVICE : ANDROID VERSION 10 & ABOVE BASED MOBILE PHONE WITH NFC MODULE READY; iv) REMOTE REAL TIME MONITORING AND MANAGEMENT SYSTEM : NO; v) AMBIENT TEMPERATURE : -10 °C TO 55 °C; vi) RELATIVE HUMIDITY : 5% TO 95%; vii) DEGREE OF PROTECTION : IP 54 AT PANEL; viii) FAULT RECORD : YES; ix) EVENT RECORD : YES; x) BUILT-IN SELF-TEST/DIAGNOSTIC : YES (INTERNAL RELAY FAILURE – IRF); xi) EXTERNAL ALARM CONTACT FOR PROTECTION RELAY FAILURE/DEFECT : YES; xii) OTHER(S) : SELF-RECLOSE (RX 330 ONLY)
Negara MALAYSIA

BilMODELPOWER SUPPLYMOUNTING TYPETIME DELAY SETTING RANGESSENSITIVITY SETTING RANGESGambar
1RX 300198 ~ 265 VAC, 50/60 Hz PANEL FLUSH0 s TO 10 s0.02 A TO 30 A
2RX 330198 ~ 265 VAC, 50/60 Hz PANEL FLUSH0 s TO 10 s0.02 A TO 30 A
Senarai Dokumen Berkaitan :