Keterangan Barangan | MOULDED CASE CIRCUIT BREAKER (MCCB) |
Kod Barangan | EE031402.ME37.A114 |
Nama Syarikat | ABB MALAYSIA SDN. BHD. |
Status Syarikat | PEMBEKAL |
Alamat | SUNWAY REIT INDUSTRIAL - BUILDING P1 LOT 3, JALAN SS 8/6, SUNGAI WAY |
| 47300 PETALING JAYA SELANGOR |
No Telefon | 0356284888 |
No Fax | 0356327889 |
Email | contact.center@my.abb.com |
Website | www.abb.com.my |
Jenama | ABB |
No Laporan | i) SIJIL UJIAN CB (CQC) : CN53589-M2, CN53590, CN53590-A1 & CN54980
ii) LAPORAN UJIAN CB (CQC) : 00901-CB2021CQC-096130-M2, 00901-CB2021CQC-096129,
00901-CB2021CQC-096129-A1 & 00901-CB2021CQC-096934 |
Tarikh Tamat | 15-02-2027 |
Rujukan | IEC 60947-2:2016 (5th Edition) & IEC 60947-2:2016 + A1:2019 |
Catatan | 1) SACE FORMULA DSP SERIES
2) REFERENCE TEMPERATURE : 40°C |
Bil | Model | RATED CURRENT (A) | UTILIZATION CATEGORY | NO. OF POLE | Icu (kA) | Ics (kA) (Ics = 100% Icu) | TRIP UNIT | SETTING OF PROTECTION | "WEIGHT (kg) (approx.)" | Column Name | Gambar |
1 | P1B 160
| 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 & 160
| A | 3 & 4
| 18 | 18 | THERMAL MAGNETIC
| ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.1 & 1.4
| | |
2 | P1C 160
| 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 & 160
| A | 3 & 4
| 25 | 25 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.1 & 1.4 | | |
3 | P1N 160
| 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 & 160
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.1 & 1.4 | | |
4 | P1S 160
| 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 & 160
| A | 3 & 4 | 50 | 36
(Ics = 72% Icu)
| THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.1 & 1.4 | | |
5 | P2C 250
| 200 & 250
| A | 3 & 4 | 25 | 25 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.7 & 2.1
| | |
6 | P2N 250
| 200 & 250
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.7 & 2.1
| | |
7 | P2S 250
| 200 & 250
| A | 3 & 4 | 50 | 36
(Ics = 72% Icu)
| THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC
| 1.7 & 2.1 | | |
8 | P3N 400
| 320 & 400
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC
(Ii : (5 - 10) X In)
| 3.25 & 4.15
| |   |
9 | P3S 400
| 320 & 400 | A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC
(Ii : (5 - 10) X In)
| 3.25 & 4.15 | | |
10 | P3N 630
| 630 | A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC
(Ii : (5 - 10) X In)
| 3.25 & 4.15 | | |
11 | P3S 630
| 630 | A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC
(Ii : (5 - 10) X In)
| 3.25 & 4.15 | | |