Bil | MODEL | RATED CURRENT (A) | UTILIZATION CATEGORY | NO. OF POLE | Icu (kA) | Ics (kA)(Ics=100% Icu) | TRIP UNIT | SETTING OF PROTECTION | WEIGHT(kg)(approx) |
1 | CVS 100B | 16, 25, 32, 40, 50, 63, 80 & 100
| A | 3 & 4 | 25 | 25 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 1.8 & 2.2 |
2 | CVS 100F | 16, 25, 32, 40, 50, 63, 80 & 100
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 1.8 & 2.2 |
3 | CVS 100N | 16, 25, 32, 40, 50, 63, 80 & 100
| A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 1.8 & 2.2 |
4 | CVS 160B | 125 & 160
| A | 3 & 4 | 25 | 25 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 1.8 & 2.3 |
5 | CVS 160F | 125 & 160
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 1.8 & 2.3 |
6 | CVS 160N | 125 & 160
| A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 1.8 & 2.3 |
7 | CVS 250B | 200 & 250
| A | 3 & 4 | 25 | 25 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 2.0 & 2.6 |
8 | CVS 250F | 200 & 250
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 2.0 & 2.6 |
9 | CVS 250N | 200 & 250
| A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
FIXED MAGNETIC"
| 2.0 & 2.6 |
10 | CVS 400F | 320 & 400
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC"
(li : 2000A - 4000A) | 4.7 & 6.3 |
11 | CVS 400N | 320 & 400
| A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC"
(li : 2000A - 4000A) | 4.7 & 6.3 |
12 | CVS 630F | 500 & 600
| A | 3 & 4 | 36 | 36 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC"
(li : 2500A - 5000A) | 5.2 & 7.1 |
13 | CVS 630N | 500 & 600
| A | 3 & 4 | 50 | 50 | THERMAL MAGNETIC | "ADJUSTABLE THERMAL
(Ir : (0.7 - 1.0) X In)
ADJUSTABLE MAGNETIC"
(li : 2500A - 5000A) | 5.2 & 7.1 |