Bil | TYPE OF PROTECTION | MODEL | KETERANGAN BAHAN/BARANGAN | POWER SUPPLY | TIME DELAY SETTING RANGES | CURRENT SETTING RANGES |
1 | OVERCURRENT PROTECTION & EARTH FAULT PROTECTION | X60 | COMBINED OVERCURRENT & EARTH FAULT RELAY (INVERSE/DEFINITE TIME DELAY/IDMT) | OPERATING VOLTAGE:
X60-OCEF-240AD:
85~265 VAC OR 110~370 VDC | OVERCURRENT PROTECTION:
i) LOW SET DELAY TIME (tI>): 0.00s TO 100s;
ii) HIGH SET DELAY TIME (tI>>): 0.00s TO 100s;
iii) VERY HIGH SET DELAY TIME (tI>>>): 0.00s TO 100s;
iv) TMS (ktI): 0.01 TO 1.00;
EARTH FAULT PROTECTION:
i) LOW SET DELAY TIME (tIo>): 0.00s TO 100s;
ii) HIGH SET DELAY TIME (tIo>>): 0.00s TO 100s;
iii) TMS (ktIo): 0.01 TO 1.00 | OVERCURRENT PROTECTION:
i) LOW SET CURRENT, (I>):
0.1 TO 25 X In, 2 X In (FOR IDMT);
ii) HIGH SET CURRENT, (I>>):
0.5 TO 40 X In;
iii) VERY HIGH SET CURRENT (I>>>):
0.5 TO 40 X In;
EARTH FAULT PROTECTION:
i) LOW SET CURRENT, (Io>): 0.02 TO 2 X Ion, 0.5 X Ion FOR IDMT;
ii) HIGH SET CURRENT, (Io>>): 0.1 TO 10 X In |
2 | OVERCURRENT PROTECTION & EARTH FAULT PROTECTION | MK3000L
| COMBINED OVERCURRENT & EARTH FAULT RELAY (INVERSE/DEFINITE TIME DELAY/IDMT) | OPERATING VOLTAGE: MK3000L-240AD: 85~265 VAC OR 110~370 VDC
| OVERCURRENT PROTECTION: i) LOW SET DELAY TIME (tI>): 0.00s TO 100s; ii) HIGH SET DELAY TIME (tI>>): 0.00s TO 100s; iii) VERY HIGH SET DELAY TIME (tI>>>): 0.00s TO 100s; iv) TMS (ktI): 0.01 TO 1.00; EARTH FAULT PROTECTION: i)LOW SET DELAY TIME (tIo>): 0.00s TO 100s; ii) HIGH SET DELAY TIME (tIo>>): 0.00s TO 100s; iii) TMS (ktIo): 0.01 TO 1.00 | OVERCURRENT PROTECTION: i) LOW SET CURRENT, (I>): 0.1 TO 25 X In, 2 X In (FOR IDMT); ii) HIGH SET CURRENT, (I>>): 0.5 TO 40 X In; iii) VERY HIGH SET CURRENT (I>>>): 0.5 TO 40 X In; EARTH FAULT PROTECTION: i) LOW SET CURRENT, (Io>): 0.02 TO 2 X Ion, 0.5 X Ion (FOR IDMT); ii) HIGH SET CURRENT, (Io>>): 0.1 TO 10 X In; iii) VERY HIGH SET CURRENT (Io>>>): 0.1 TO 10 X In |