Keterangan Barangan | COMBINED OVERCURRENT AND EARTH FAULT RELAY |
Kod Barangan | EE031201.ME120.A129 |
Nama Syarikat | DELAB SCIENTIFIC SDN BHD |
Status Syarikat | PENGILANG |
Alamat | NO. 22, JALAN TEMBAGA SD5/2D |
| 52200 BANDAR SRI DAMANSARA WILAYAH PERSEKUTUAN KUALA LUMPUR |
No Telefon | 0362726506 |
No Fax | 0362726915 |
Email | steven@delab.com.my |
Website | www.delab.com.my |
Jenama | DELAB |
No Laporan | LAPORAN UJIAN SIRIM : 2015RE632 |
Tarikh Tamat | 15-06-2026 |
Rujukan | i) SAFETY STANDARD : IEC 60255-27:2013 (10.6.4.2 IMPULSE VOLTAGE WITHSTAND & CLAUSE 10.6.4.3 DIELECTRIC TEST)
ii) EMC STANDARD : IEC 60255-26:2013 (CLAUSE 5.1, 7.2.3, 7.2.4, 7.2.5, 7.2.6, 7.2.7, 7.2.8, 7.2.10 & 7.2.11) |
Catatan | i) COMMUNICATION INTERFACE : RS 485 (EXTERNAL MODULE IS REQUIRED);
ii) COMMUNICATION PROTOCOL : MODBUS RTU (EXTERNAL MODULE IS REQUIRED);
iii) COMMUNICATION DEVICE : PERSONAL COMPUTER (EXTERNAL MODULE IS REQUIRED);
iv) REMOTE REAL TIME MONITORING AND MANAGEMENT SYSTEM : YES (EXTERNAL MODULE IS REQUIRED)
v) AMBIENT TEMPERATURE : 0 °C TO 55 °C;
vi) RELATIVE HUMIDITY : 93%;
vii) DEGREE OF PROTECTION : IP 54 AT PANEL;
viii) FAULT RECORD : YES;
ix) EVENT RECORD : YES;
x) BUILT-IN SELF-TEST/DIAGNOSTIC : YES (DEVICE FAILURE - DUF);
xi) EXTERNAL ALARM CONTACT FOR PROTECTION RELAY FAILURE/DEFECT: YES;
xii) OTHER(S) : LATEST FIRMWARE REVISION : 2.06 |
Bil | MODEL | POWER SUPPLY | MOUNTING TYPE | TIME DELAY SETTING RANGES | CURRENT SETTING RANGES | Gambar |
1 | DP-34 | 65 ~ 275 VAC,
45 ~ 65 Hz
OR
90 ~ 300 VDC
| OVER CURRENT PROTECTION | a) LOW SET TIME DELAY SETTING (tp>):
i) TMS FOR INVERSE TIME DELAY (TMS Ip>):
0.05 TO 1
ii) DELAY FOR DEFINITE TIME:
0.03 s TO 20 s
___________________________
b) HIGH SET TIME DELAY SETTING (tp>>):
0 s OR 0.02 s TO 0.5 s
| a) LOW SET OVER CURRENT SETTING (Ip>):
2% TO 200% OF In
__________________________
b) HIGH SET OVER CURRENT SETTING (Ip>>):
20% TO 2000% OF In
| |
2 | DP-34 | 65 ~ 275 VAC, 45 ~ 65 Hz OR 90 ~ 300 VDC | EARTH FAULT PROTECTION | a) LOW SET TIME DELAY SETTING (te>):
i) TMS FOR INVERSE TIME DELAY (TMS Ie>):
0.05 TO 1
ii) DELAY FOR DEFINITE TIME:
___________________________
0.03 s TO 20 s
b) HIGH SET TIME DELAY SETTING (te>>):
0 s OR 0.02 s TO 0.5 s | a) LOW SET EARTH FAULT SETTING (Ie>):
2% TO 100% OF In
__________________________
b) HIGH SET EARTH FAULT SETTING (Ie>>):
20% TO 1000% OF In
| |